4C x 1.5mm² – VSD04/1.5


PCW X-90 Insulated

Applications
Suitable for use with VSD’s where RFI & EMI, protection is required
Suitable for fixed installations.
Rated voltage 0.6/1Kv

Specification Sheet:
  Click to download specifications

4 Core 30/0.25mm (1.5mmsq)
P.C.W. X-90 (XLPE)
VSD Cable 0.6/1Kv to AS/NZS5000.1.
Oxygen-Free Copper. RoHS Compliant.

Construction

Conductor:

PHASE: 30 strands of 1.5mm nom. Stranded Tinned Copper to AS1125 drawn from Class 5 Copper IEC60228
Max. D.C. resistance at 20C: 12.5 ohms / km.

EARTH: 30 strands of 0.25 mm nom. Stranded Tinned Copper to AS1125 drawn from Class 5 Copper IEC60228
Max. D.C. resistance at 20C: 12.5 ohms / km.

Insulation:

ACTIVE & NEUTRAL: Coloured X-90 to AS/NZS 3808.
Nominal Diameter: 3.0 mm.
Nominal Wall Thickness: 0.7 mm.

EARTH: Coloured X-90 to AS/NZS 3808.
Nominal Diameter: 3.0 mm.
Nominal Wall Thickness: 0.7 mm.

Lay Up: 4 Cores laid up.

ACTIVE:

1. Red
2. White
3. Blue

EARTH:

4. Lt Green / Yellow

First Shield:
Material AL/pet tape
Construction Overall & helically wrapping, 100% coverage

Second Shield
Material Tinned Copper Wire
Construction 24*8*0.12mm, braiding coverage 85%

Jacket
Material Black 5V 90 PVC, UV Stabilized
Nominated External Target Diameter: 11.6 mm.
Nominal Wall Thickness: 1.8 mm.

Cable Weight 196kg/Km

Identification: Printed on the sheath – TYCAB (YEAR 2023) ELECTRIC CABLE 5V-90 0.6/1Kv – VSD04/1.5 3 x 1.5mm2 + Earth 1.5 mm2