Specification Sheet:
Click to download specifications
7/1.70(16.0mmsq) Plain Copper Wire
Construction
Conductor: 7 strands of 1.70mm Plain Annealed Copper, Conventional Concentric Laid-Up Circular Stranded Conductor to AS/NZS 1125 CLASS 2
Max. D.C. resistance at 20C: 1.15 ohms / km.
Nominal O.D.(mm): 5.15
Features:
1. Oxygen Free High Conductivity copper with excellent electric and thermal conductivity properties.
2. Excellent hydrogen embrittlement resistance, (TPC ) Tough pitch copper becomes very brittle when it is heated at higher than 6000C under a reducing gas atmosphere including hydrogen. Since OFHC contains a very low oxygen content, it does not show any brittleness.
3. Class 2 Conductor.
Reference Standards:
AS1125 Max. conductor Resistance
AS3808 INSULATION and sheath compound type.
AS5000 Construction to 0.6/1KV sheathed single core for fixed applications CABLE TESTS TO TABLE 5 AS APPLICABLE
AS3008 Power Amp Ratings, Voltage Drop, Derating Factors.